YX3000 series PID Parameters Setting:
P7.00=1
P7.01=0
P7.02=0
P7.05=0.300, this is the given pressure, increase the value if the pressure is not enough P7.19=0.200, this parameter is the pressure setting after the sleep pressure goes down to the set value and starts running automatically. Set according to the actual requirements of the site.
P7.20=0.320, this parameter is the dormant pressure, and the general setting is about 0.020 larger than the set pressure.
P7.21= After the pressure reaches the sleep pressure, it will sleep after the running time. According to the actual setting time, the default is 10 seconds.
P7.22=25 Minimum operating frequency of sleep.
P7.23= This is the sleep frequency time, according to the actual settings. The default is to enter the shutdown sleep after 10 seconds.
P7.26=1
P7.27=1